| Online UPS Max-Series |
| |
|
|
Applications:
Small computer network, servers, cyber café, banks and offices.
Features:
- High frequency and Double Conversion online technology
- High end Micro Controller based
- Wide Input voltage range
- Advanced PFC Technology
- Advanced Battery Management
- Automatic Battery charging in UPS off mode
- Short circuit and Overload Protection
- EMI/RFI Noise Filter
- Smart RS232 Communication with monitoring software
- SNMP card slot (optional)
- LCD/LED Display simultaneously
- Specially Designed to suit Indian power and environment conditions
- Generator Compatible
- Isolation Transformer (optional).
|
 |
| Max-Series 1KVA ~ 3KVA |
|
|
|
|
| |
| Model |
MAX-SERIES |
036MX1KK11 |
096MX2KK11 |
096MX3KK11 |
| Capacity |
|
1KVA/700W |
2KVA/1400W |
3KVA/2100W |
| Input |
Voltage Range |
When load<50%, range is 118±5VAC~295±5VAC |
| |
|
When ≥ 50% load, input range is 160±5VAC~295±5VAC |
| |
Frequency |
46~54Hz±0.5Hz |
| |
Phase |
Single Phase |
| |
Input Power Factor |
≥0.95 |
≥0.97 |
≥0.97 |
| Output |
Voltage Range |
220V±2% |
| |
Frequency Range |
50Hz±0.2% |
| |
THD (Linear Load) |
<3% |
| |
THD (Non-Linear Load) |
<5% |
| |
Overload Capability |
>110%, 30s turn to bypass mode; |
| |
>150%, 200ms turn to bypass |
| |
Crest Factor |
3:1 (max) |
| |
Short Circuit Protection |
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode), |
| |
|
5 cycles turn off inverter, provide alarm (battery mode), input fuse blown or breaker action |
| |
Waveform |
Pure Sine Wave |
| |
Transfer time AC to Bypass mode |
4ms (typical 2.5ms) |
| |
Efficiency |
≥80% |
≥85% |
≥80% |
| Battery |
DC Voltage |
36VDC/48VDC |
96VDC/120VDC |
96VDC/120VDC |
| |
Charge Current |
0.5A~10A |
0.5A~10A |
0.5A~10A |
| Communication Interface |
RS232; SNMP (optional) |
| LED/LCD Indication |
Load or battery capacity |
| Noise Level |
<45dB |
| Dimensions Product |
144 x 412 x 213 |
191 x 470 x 338 |
191 x 470 x 338 |
|
|
| |
|