| Online UPS SuperMax-Series-I |
| |
|
Applications:
Networking equipments, computer rooms, mission critical process, banks, offices, railways, airport, hospitals, defence and telecom centers, all type of Single Ph. Loads |
|
|
Features:
- True online Double Conversion technology
- High end Micro Controller
- Automatic battery charging in UPS off mode
- Wide Input voltage range
- Advanced Battery Management
- Short circuit and Overload Protection
- Parallel Redundant/Hot Standby. (Optional)
- Galvanic Isolation
- 1 Phase in ~ 1 Phase out (upto 10KVA)
- 3 phase in ~ 1 Phase out (upto 30KVA)
- Specially Designed to suit Indian power and environment conditions
- Generator Compatible
|
|
|
|
|
| |
| Model |
|
SUPERMAX-SERIES-I |
| Capacity |
|
5KVA to 30KVA |
| Technology |
|
Double Conversion High Freq. switching PWM, using IGBT's |
| Input |
Voltage Range |
160V AC~270V AC ±5V AC, Single Phase for upto 10KVA and 360V AC~450V AC ±5V AC, Three Phase for upto 30KVA |
| |
Frequency |
45~55Hz |
| |
Phase |
Single Phase upto 10KVA and Three Phase from 5 to 30KVA |
| |
Generator Compatibility |
Present |
| Output |
Voltage |
230V AC ±1% |
| |
Frequency Range |
50Hz±0.5% |
| |
THD (Linear Load) |
<3% |
| |
THD (Non-Linear Load) |
<5% |
| |
Overload Capability |
125% for 2minutes / 150% for 30Seconds |
| |
Crest Factor |
3:1 (max) |
| |
Short Circuit Protection |
Instant |
| |
Waveform |
Pure Sine Wave |
| |
Manual Bypass |
inbuilt upto 15KVA |
| |
Static Bypass (optional) |
<5ms |
| |
Inverter Efficiency |
≥90% on rated full load |
| |
Overall Efficiency |
≥80% |
| Battery |
DC Voltage |
180 / 360 VDC |
| Mimic Control Panel |
LED for UPS status and LCD for Voltage, Current & Frequency |
| Audible Alarm |
For Battery Low / DC High / Output High / Overload |
| Noise Level |
≤50dB |
| Transient Response |
for 100% Step Load charge, ±5% and recovers to normal within 20 milliseconds. |
| Ambient Temperature / Relative Humidity |
0-45° C / 0-95% Non-Condensing |
| Cooling |
Forced Aircooled |
|
|
| |
|